40 C.F.R. § 60.55b
40 C.F.R. § 60.55b
US-DOC-26830285
locator
Regulation details
Full name
Code of Federal Regulations
Bluebook Citation
40 C.F.R. § 60.55b
Country
United States
Jurisdiction
Federal
§ 60.55b Standards for municipal waste combustor fugitive ash emissions.
(a) On and after the date on which the initial performance test is completed or is required to be completed under § 60.8 of subpart A of this part, no owner or operator of an affected facility shall cause to be discharged to the atmosphere visible emissions of combustion ash from an ash conveying system (including conveyor transfer points) in excess of 5 percent of the observation period (i.e., 9 minutes per 3-hour period), as determined by EPA Reference Method 22 observations as specified in § 60.58b(k), except as provided in paragraphs (b) and (c) of this section.
(b) The emission limit specified in paragraph (a) of this section does not cover visible emissions discharged inside buildings or enclosures of ash conveying systems; however, the emission limit specified in paragraph (a) of this section does cover visible emissions discharged to the atmosphere from buildings or enclosures of ash conveying systems.
(c) The provisions specified in paragraph (a) of this section do not apply during maintenance and repair of ash conveying systems.
[60 FR 65419, Dec. 19, 1995, as amended at 62 FR 45126, Aug. 25, 1997]